Helukabel H07RN-F / 07RN-F

Technical Data Rubber connection cable, H07RN-F acc. to DIN VDE 0285- 525-2-21 / DIN EN 50525-2-21; 07RN-F in alignment with DIN VDE 0285-525-2-21 / DIN EN 50525-2-21
Temperature Range flexible -25°C to +60°C
fixed -30°C to +60°C
Nominal Voltage AC U0/U 450/750 V
Test Voltage 2500 V
Minimum Bending Radius fixed 4x Outer-Ø
flexible, guidance via roles 7.5x
Outer-Ø
flexible, winding on drums 5x
Outer-Ø
Cable Structure • Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 /
IEC 60228 Class 5
• Core insulation: rubber acc. to DIN VDE 0207-363-1 /
DIN EN 50363-1 (compound type EI4)
• Core identification acc. to DIN VDE 0293-308,
1 core(s): black
2 – 5 core(s): colour coded
7 – 37 core(s): black cores with consecutive labeling in white digits
• Protective conductor: starting with 3 cores,
G = with protective conductor GN-YE, in the outer layer,
x = without protective conductor
• Cores stranded in layers with optimal lay lengths
• Outer sheath: rubber acc. to DIN VDE 0207-363-2-1 /
DIN EN 50363-2-1 (compound type EM2)
• Sheath colour: blac
Test • flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-
1-2 / IEC 60332-1-2
• oil-resistant acc. to DIN VDE 0473-811-404 / DIN EN 60811-404
/ IEC 60811-404
• certifications and approvals:
H07RN-F: HAR
EAC
Application Heavy duty, rubber sheathed cable for use with medium mechanical
stress in dry, damp, wet rooms, in agricultural premises and outdoors. Suitable for equipment in commercial operations, e.g. heating
plates, hand lamps, electric tools such as drills or circular saws. For
fixed installation on plaster as well as in temporary constructions. When installed in pipes or similar enclosed systems, the use of
the cable is permitted up to and including 1000 V AC voltage or up to
750 V DC voltage against earth.