Show Sidebar

Cables

Showing 13–24 of 31 results

  • Helukabel Helusound® 600 FRNC

    Cable Structure Conductor material: Copper, bare
    Core insulation: FRNC
    Core colours: rd, bk
    Stranding element: pairs stranded
    Sheath material: FRNC
    Cable external diameter: approx. 6,6 mm
    Sheath colour: black
    Application The safe solution for increasing demands on the security in case of fire, as flame retardant, low smoke, halogen-free, no corrosion damage by released
    gases and fumes, no flame propagation provide for local flame propagation for the integrity of important systems.

     

  • Helukabel Insulated Grounding Cable

    Description  Class 5 bare Cu-conductor (IEC 60228)
    Very Flexible; minimal bending radius
    Available in different electrical primary color
    Special TI1 PVC insulation
    Flame retardant per IEC 60332-1
    ≈10 MOhm x km insulation resistance
    Nominal voltage up to 1000V
    750V direct current against earth
    Harmonized CE approved product conformed with EC
    low voltage directive 2006/95/EC
    100mtr/box available for size ≤10mm²
    High ambient temperature compare to other local type
    •GN-YE grounding conductor is also available

     

  • Helukabel JZ-600

    Description UV resistant
    For outdoor use
    Largely oil resistant
    For outer diameters larger than 18.00mm, suitable for direct burial
    Versatile use in many industries, particularly in machine and plant construction
    Application Used as a connection and control cable in machine tools, assembly lines and conveyor belts, production lines, in plant construction, heating and air-conditioning technology, in smelters and steel mills. Suitable for flexible applications involving medium mechanical stress with free movement, without tensile stress and without forced motion control in dry, damp and wet rooms, as well as outdoors (fixed installation). May not be laid directly in soil (suitable for direct burial starting with an outer diameter of 18.0 mm) or water.

     

  • Helukabel NANOFLEX® HC*500c

    Temperature Range flexing -5 °C to +80 °C
    fixed installation -40 °C to +80 °C
    Nominal Voltage UL/CSA 600V
    U0/U 300/500 V
    Test Voltage 4000 V
    Breakdown Voltage min. 8000 V
    Minimum Bending Radius flexing 7.5x cable ø
    fixed installation 4x cable ø
    Cable Structure Bare copper conductor, fine wire stranded according to DIN VDE 0295 cl. 5, BS 6360cl. 5 or IEC 60228 cl. 5
    Special PVC conductor insulation TI2 according to DIN VDE 0281 Part 1
    Black conductors with sequential white numbering in accordance with DIN VDE 0293 Green-yellow ground in the outer layer, 3 cores and more
    Conductors stranded in layers with optimal lay-lengths
    Outer jacket from special full polyurethaneTMPU according to DIN EN 50363-10-2 With meter marking

     

  • Helukabel NEOPREN

    Technical Data Special rubber cable  adapted to DIN VDE 0250
    Temperature Range flexing -25°C to +60°C fixed installation -40°C to +80°C
    Nominal Voltage U0/U 300/500 V
    Test Voltage 3000 V
    Minimum Bending Radius for continuous bending without forced guiding operation 12,5x cable Ø
    for flexing with forced guiding operation 20x cable Ø
  • Helukabel NSSHÖU heavy dusty rubber cable 0,6/1kV

    Technical Data Rubber sheath cable to DIN VDE 0250 part 812
    Temperature Range flexing -25°C to +80°C
    fixed installation -40°C to +80°C
    ● Resistant against hot penetration
    ● Core insulation of rubber (EPR)
    compound type 3GI3 to
    DIN VDE 0207 part 20
    ● Low abrasion
    ● High notch resistant
    ● Permissible operating temperature
    at conductor +90°C
    Nominal Voltage U0/U 0,6/1 kV
    Test Voltage 3000 V
    Minimum Bending Radius fixed installation 4x cable Ø
    flexing 10x cable Ø
    without forced operation 15x cable Ø
    Cable Structure Tinned copper-conductor, to
    DIN VDE 0295 cl.5, fine-wire,
    BS 6360 cl.5, IEC 60228 cl.5
    Core insulation of rubber (EPR)
    compound type 3GI3 to DIN VDE 0207 part 20
    Core identification to DIN VDE 0293-308
    – up to 5 cores coloured
    – from 6 cores, black with continuous white numbering
    GN-YE conductor,  3 cores and above
    Cores stranded in layers with optimal lay-length
    Test Behaviour in fire to DIN VDE 0482-332-1-2 DIN EN 60332-2-1, IEC 60332-1 (equivalent
    DIN VDE 0472 part 804 test method B) Oil resistant to DIN EN 60811-404
  • Helukabel Profibus L2

    Description Profibus acc. to DIN 19245 T3 and EN50170 Flame-retardant acc. IEC 60332-2-1
    Cable Structure Inner conductor diameter: Copper, bare (AWG 24/7)
    Core insulation: Foam-skin-PE
    Core colours: rd, gn
    Stranding element: 2 cores + 2 fillers stranded together
    Separator: Polyester foil over stranded bundle
    Shielding 1: Al-Foil
    Total shielding: Cu braid, tinned
    Outer sheath material: PVC
    Cable external diameter: app. 7,8 mm ± 0,3 mm
    Outer sheath colour: Violet similar to RAL 4001
    Test Test voltage: 1,5 kV Attenuation: dB/km 9,6 kHz < 2,9 38,4 kHz < 4,6 dB/km 4 MHz < 25,0 dB/km 16 MHz < 49,0 dB/km
    Application Profibus L2 7-wire for mobile applications in Profibus industrial networks. With its core design and the special PVC sheath, the type
    described here is suitable for normal mobile applications.

     

  • Helukabel PVC Single Core H07V-K

     

    Temperature Range flexible +5°C to +70°C fixed -30°C to +80°C
    Nominal Voltage AC U0/U 450/750 V
    Test Voltage 2500 V
    Minimum Bending Radius fixed
    <8 mm: 4x Outer-ø
    8-12 mm: 5x Outer-ø
    >12 mm: 6x Outer-ø
    Cable Structure Copper wire bare, finely stranded acc. to DIN VDE 0295 Class 5 /
    IEC 60228 Class 5
    Core insulation: PVC acc. to DIN VDE 0207-363-3 /
    DIN EN 50363-3 (compound type TI1)
  • Helukabel RE-2Y(St)Yv

    Description Computer cable
    reinforced outer sheath
    with drain wire
    Suitable for outdoor use (for fixed installations)
    with blue outer sheathing: for intrinsically safe systems in explosion-endangered areas
    Cable Structure Copper wire bare, stranded
    Wire structure:
    0.5 mm²: 7 x 0.3 mm
    0.75 mm²: 7 x 0.37 mm
    1.3 mm²: 7 x 0.49 mm
    Core insulation: PE
    Core identification: colour coded, pairs:
    a-core = black; b-core = white
    with consecutive numbering 1/1, 2/2, etc.,
    triads: a-core = black; b-core = white; c-core = red
    Cores stranded in pairs / triads with optimal lay lengths, Pairs stranded in layers with optimal lay lengths
    for multiple pair design: communication core, nominal cross-section: 0.5 mm², Core insulation: PE, Core identification: orange
    Foil wrapping
    Drain wire, tinned copper, stranded (0.5 mm² = 7 x 0.3 mm)
    Screen: plastic-coated aluminium foil (St), approx. overlap 25%
    Outer sheath: PVC, reinforced (v)
    Sheath colour: see datasheet
    Length marking: in metres
    Test flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
    certifications and approvals:
    EAC
    Application Instrumentation cables are used in data processing and process control. Low level of line attenuations and low mutual capacitances enable long transmission distances and fast pulse acceleration. Instrumentation cables are suitable for fixed installations in damp locations, in open spaces and for underground laying.
  • Helukabel SiF

    Description Silicone single core
    finely stranded
    tinned wire
    increased temperature resistance
    Cable Structure Copper wire tinned, finely stranded, 0.5 – 185 mm²: acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
    Wire structure:
    0.25 mm²: approx. 8 x 0.2 mm
    Core insulation: silicone
    Core identification: see datasheet
    Test halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
    corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
    flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
    certifications and approvals:
    EAC
    Application Temperature resistant silicone single core for use in iron, steel and rolling mills, foundries, cement, glass and ceramic factories as well as in aircraft construction and ship building.
  • Helukabel SiF/ GL

    Description Spezial-silicon single core with higher  heat-resistance range adapted to DIN VDE 0250 Teil 1 and part 502
    Cable Structure Tinned copper-conductor, from 0,5 mm² to
    DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5                                                                                                                                                                           Conductor construction: 0,25 mm² = 14×0,15mm                                                                                                                                                                                                                                                                                                                                Core insulation of silicone                                                                                                                                                                                                                                                                                                                        Glass-fibre braiding
    Test Corrosiveness of combustion gases (Halogen-free) acc. to DIN VDE 0482 part 267, DIN EN 50267-2-2, IEC 60754-2 (equivalent DIN VDE 0472 part 813) Behaviour in fire no flame propagation acc. to DIN VDE 0482-332-1-2, DIN EN 60332-1-2,IEC 60332-1 (equivalent
    DIN VDE 0472 part 804 test method B)
    Application Special single cores for use in high, resp. low temperature areas. They are used mainly in the steel producing industries, in aviation industries as well
    as in ship building, cement, glas and ceramic factories. As this single cores are halogen-free, especially suited for use in power stations.
    = The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

     

  • Helukabel SiHF

    Description Silicone cable
    increased temperature resistance
    tinned wire
    Cable Structure Copper wire tinned, finely stranded acc. to DIN VDE 0295 Class 5 / IEC 60228 Class 5
    Core insulation: silicone
    Core identification acc. to DIN VDE 0293-308,
    2 – 5 core(s): colour coded
    6 – 25 core(s): black cores with consecutive labeling in white digits
    Protective conductor: starting with 3 cores,
    G = with protective conductor GN-YE, in the outer layer,
    x = without protective conductor
    Cores stranded in layers with optimal lay lengths
    Outer sheath: silicone
    Sheath colour: redbrown
    Length marking: in metres
    Test halogen-free acc. to DIN VDE 0482-754-1 / DIN EN 60754-1 / IEC 60754-1
    corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2
    flame-retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2
    certifications and approvals:
    EAC
    Application Silicone cables were evolved for use wherever insulation is subjected to extreme temperature changes. The good performance of the environmental resistant properties means that silicone cables can be used at temperatures down to -60°C. Silicone cables are halogen-free cables and are especially suited for installation in power stations. They have also found their uses in the steel producing industries, aviation industry, ship building as well as in ceramic, glass and cement factories. Due to elastical characteristic of core insulations, these are used as flexible connection cable