Show Sidebar

Search Results for: citel

Citel-MJ8-CAT6S

Citel-MJ8-CAT6S

Network
Gigabit Ethernet, Cat.6 cabling
Max. DC operating voltage
Uc 8 Vdc
Max. frequency
f max. > 250 MHz
Max. data rate
10/100/1000 Mbps
Insertion loss
< 1 dB
Max. load current
@25°C
IL 1000 mA
Max. capacitance
C < 25 pF
Impulse current
2 x 10/350µs Test – D1 Category
Iimp 500 A
Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 – C2 Category
In L/PE 2000 A
Citel- MJ6-1T/D

Citel- MJ6-1T/D

  • Telecom line surge protector
  • PSTN, ADSL2, VDSL
  • 1-pair + Shielded
  • Instantaneous installation
  • RJ11 connector
  • UL497A
    Network
    Telephone Line, ADSL2, VDSL2, 1 pair
    Nominal line voltage
    Un 150 Vdc
    Max. DC operating voltage
    Uc 170 Vdc
    Max. frequency
    f max. > 10 MHz
    Max. data rate
    30 Mbps
    Insertion loss
    < 1 dB
    Max. load current
    @25°C
    IL 300 mA
    Protection level
    @ In (8/20µs)
    Up 220 V
    Protection level
    @ In (8/20 µs)
    Up L/L 220 V
    Protection level L/N
    @ In (8/20µs)
    Up L/N 220 V
    Protection level L/PE
    @ In (8/20µs)
    Up L/PE 220 V
    Max. capacitance
    C < 70 pF
    Impulse current
    2 x 10/350µs Test – D1 Category
    Iimp 500 A
    Line/Line Nominal discharge current
    C2 Category
    In L/L 2500 A
    Nominal Discharge Current, X-C (Line/Earth)
    8/20µs Test x 10 – C2 Category
    In L/PE 2500 A

 

Citel- DLU-48D3

Citel- DLU-48D3

etwork
48 V line, ISDN-T0, Profibus-PA
Nominal line voltage
Un 48 V
Max. DC operating voltage
Uc 53 Vdc
Max. frequency
f max. > 3 MHz
Insertion loss
< 1 dB
Max. load current
@25°C
IL 300 mA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 20 kA
Line inductance
No
Protection mode(s)
Common/Differential mode
Protection level
@ In (8/20 µs)
Up L/L 70 V
Max. capacitance
C < 50 pF
Impulse current
2 x 10/350µs Test – D1 Category
Iimp 5 kA
Nominal discharge current
C2 Category
In 5 kA
Line resistance
< 4.7 Ohm
Citel-DLC-06D3

Citel-DLC-06D3

  • High speed data transmission
  • Common mode and differential mode protection
  • Data lines, including those isolated from Earth
  • Compact DIN rail enclosure, high density protection
  • Protection of shield wire
  • Location and test categories: D1, C2, C3
  • IEC 61643-21 compliance
Citel- DLAS-24D3

Citel- DLAS-24D3

Network
4-20 mA
Max. DC operating voltage
Uc 28 Vdc
Max. frequency
f max. > 3 MHz
Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 – C2 Category
In L/PE 5 kA
DATA SPD TYPE
UL497B LISTED
VOLTS
(V) 24
WIRES
RJ11 Connector
LINE CURRENT MAX
(A) 0.3
AMBIENT MIN
(C) -50
AMBIENT MAX
(C) +85
RESIDUAL VOLTAGE
(V) 40
MCOV
(V) 28/
IMAX
8/20µs
(kA) 20
Iimp
10/350µs
(kA) 5
DATA SPEED
(Mbps) up to 10MHz
INSERTION LOSS (@ FREQ)
(db) < 1
CAPACITANCE
(pF) < 50
Citel-DLA-48DBC

Citel-DLA-48DBC

Network
Fipway, WorldFIP, FieldBus-h2
Nominal line voltage
Un 48 V
Max. DC operating voltage
Uc 53 Vdc
Max. frequency
f max. > 20 MHz
Insertion loss
< 1 dB
Max. load current
@25°C
IL 300 mA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 20 kA
Line inductance
No
Protection level
@ In (8/20 µs)
Up L/L 75 V
Impulse current
2 x 10/350µs Test – D1 Category
Iimp 5 kA
Nominal discharge current
C2 Category
In 5 kA
Line resistance
< 4.7 Ohm
Citel- DD9-24V

Citel- DD9-24V

Network
RS232, RS485, 4-20mA
Max. DC operating voltage
Uc 40 Vdc
Max. frequency
f max. > 10 MHz
Max. data rate
< 40 Mbps
Insertion loss
< 1 dB
Max. load current
@25°C
IL 750 mA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 1125 A
Protection mode(s)
Common mode
Protection Level
C3 category (10/1000μs), 300 applications@10 A, X-X (Line/Line)
Up 130 V
Protection level
C3 category (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
Up 65 V
Nominal Discharge Current
C2 category (8/20μs), 10 applications, X-X (Line/Line)
In 125 A
Nominal discharge current
C2 category (8/20μs), 10 applications X-C (Line/Earth)
In 125 A
Capacitance
@1MHz, X-C (Line/Earth)
C < 500 pF
DATA SPD TYPE
UL497B LISTED
VOLTS
(V) 24
WIRES
9W+GROUND
AMBIENT MIN
(C) -50
AMBIENT MAX
(C) +85
RESIDUAL VOLTAGE
(V) 20
IMAX
8/20µs
(kA) 1
Iimp
10/350µs
(kA)
DATA SPEED
(Mbps) up to 10MHz
Citel-CXC06-B/FM

Citel-CXC06-B/FM

Network
coaxial DC-70 MHz
Nominal line voltage
Un 6 V
Max. DC operating voltage
Uc 8 Vdc
Max. frequency
f max. DC-70 MHz
Insertion loss
≤0.6 dB
Return loss
≥20 dB
Impedance
50 ohms
VSWR
< 1.5:1
Max. load current
@25°C
IL 0.5 A
Operating current
Continious current at Uc
Ic None
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Protection level
@ In (8/20 µs)
Up L/L 25V / 600V
Impulse current
2 x 10/350µs Test – D1 Category
Iimp 2.5 kA / 10 kA
Nominal discharge current
C2 Category
In 5 kA
Max Power
6 W
DC Pass
Yes
Citel- CRMJ8-POE

Citel- CRMJ8-POE

Electrical Characteristics
Network POE ++ and 10Gigabit Ethernet
Max. DC operating voltage Uc 60 Vdc – 650 mA
Max. frequency f max. 500 MHz
Max. data rate 10 Gbps
Insertion loss < 1 dB
Max. load current
@25°C IL 2000 mA
Impulse current
2 x 10/350µs Test – D1 Category Iimp 500 A
Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 – C2 Category In L/PE 2000 A
DATA SPD TYPE UL497B LISTED
VOLTS (V) 60
AC/DC/DC PV/RF DC
WIRES 8W+Shield+Ground
LINE CURRENT MAX (A) 1.2
POWER RATING (W) 100
AMBIENT MIN (C)-35
AMBIENT MAX (C) +85
MODES DC+-DC-,DC+-G,DC–G,SH-G
RESIDUAL VOLTAGE (V) 70
IMAX
8/20µs (kA) 16
DATA SPEED (Mbps) 10/100/1000/1000