Citel- DLU-48D3
etwork
|
48 V line, ISDN-T0, Profibus-PA | |
Nominal line voltage
|
Un | 48 V |
Max. DC operating voltage
|
Uc | 53 Vdc |
Max. frequency
|
f max. | > 3 MHz |
Insertion loss
|
< 1 dB | |
Max. load current
@25°C
|
IL | 300 mA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
Line inductance
|
No | |
Protection mode(s)
|
Common/Differential mode | |
Protection level
@ In (8/20 µs)
|
Up L/L | 70 V |
Max. capacitance
|
C | < 50 pF |
Impulse current
2 x 10/350µs Test – D1 Category
|
Iimp | 5 kA |
Nominal discharge current
C2 Category
|
In | 5 kA |
Line resistance
|
< 4.7 Ohm |
DLU surge protectors are designed to protect, against surge voltages due to lightning, terminals equipment connected to industrial buses, telecom lines or datalines. These surge protectors must be installed on symmetrical DIN rail and are available for most of the transmission lines: line voltage from 6 to 170V, bitrate up to 10 Mbit/s. These products are 1-pair surge protectors and are made with DIN rail monobloc enclosure