Citel- DLU-48D3

etwork
48 V line, ISDN-T0, Profibus-PA
Nominal line voltage
Un 48 V
Max. DC operating voltage
Uc 53 Vdc
Max. frequency
f max. > 3 MHz
Insertion loss
< 1 dB
Max. load current
@25°C
IL 300 mA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 20 kA
Line inductance
No
Protection mode(s)
Common/Differential mode
Protection level
@ In (8/20 µs)
Up L/L 70 V
Max. capacitance
C < 50 pF
Impulse current
2 x 10/350µs Test – D1 Category
Iimp 5 kA
Nominal discharge current
C2 Category
In 5 kA
Line resistance
< 4.7 Ohm

DLU surge protectors are designed to protect, against surge voltages due to lightning, terminals equipment connected to industrial buses, telecom lines or datalines. These surge protectors must be installed on symmetrical DIN rail and are available for most of the transmission lines: line voltage from 6 to 170V, bitrate up to 10 Mbit/s. These products are 1-pair surge protectors and are made with DIN rail monobloc enclosure