Helukabel NEOPREN
Technical Data | Special rubber cable adapted to DIN VDE 0250 |
Temperature Range | flexing -25°C to +60°C fixed installation -40°C to +80°C |
Nominal Voltage | U0/U 300/500 V |
Test Voltage | 3000 V |
Minimum Bending Radius | for continuous bending without forced guiding operation 12,5x cable Ø for flexing with forced guiding operation 20x cable Ø |
Cable Structure | Bare copper conductor, to DIN VDE 0295 cl.6 col.4, extra fine wire, BS 6360 cl.6, IEC 60228 cl.6 |
Core insulation of rubber • Core identification to DIN VDE 0293-308 – up to 5 cores coloured – from 6 cores, black with continuous white numbering |
|
GN-YE conductor, 3 cores and above | |
Cores stranded in layers with optimal lay length |
|
Support organ (hemp or sisal-string etc.) and/or taping with load carrying thread as construction permits | |
Outer sheath of special rubber | |
Sheath colour: black |